Skip to content

Resources

F-gas log

The F-gas log under regulation (EU) 2024/573 and the unit's status: CO2 equivalent, the leak check interval and when the next check is due. An entry takes the certificates of the company and of the person and cannot be changed afterwards, only corrected by a new entry. Adding entries needs Maci Service Premium on the unit.

The f gas entry model

Properties

  • id string (uuid)
  • unit_id string (uuid)
  • type string
  • performed_at string (date)
  • refrigerant string, nullable
  • quantity_kg number, nullable
  • reason string, nullable
  • gas_origin string, nullable
  • origin_facility_name string, nullable
  • origin_facility_address string, nullable
  • origin_certificate_no string, nullable
  • method string, nullable
  • result string, nullable
  • leak_location string, nullable
  • description string, nullable
  • disposal string, nullable
  • company_name string, nullable
  • company_cvr string, nullable
  • company_certificate_no string, nullable
  • person_name string, nullable
  • person_certificate_no string, nullable
  • corrects_entry_id string (uuid), nullable

    The entry this one corrects.

  • is_corrected boolean

    true when a later entry has corrected this one.

  • created_at string (date-time)

The f gas status model

Properties

  • unit_id string (uuid)

    The unit that holds the refrigerant.

  • refrigerant string, nullable
  • covered boolean

    Whether the unit is covered by leak checks.

  • co2e_tonnes number, nullable
  • interval_months integer, nullable

    Months between leak checks.

  • last_leak_check_at string (date), nullable
  • next_leak_check_due_at string (date), nullable
  • follow_up_check object, nullable

    The follow-up check after a repaired leak.

  • state string

    Where the unit stands towards the next check.

  • detection_system_missing boolean

    true when a leak detection system is required but missing.

GET/units/{unit}/fgas-entries

List F-gas entries

Entries in the F-gas log.

The logbook is kept on the unit that holds the refrigerant. For a unit on a central system it is the logbook of that system.

Scope: fgas:read

Path parameters

  • unit string (uuid) required

    The ID of the unit.

Query parameters

  • limit integer

    Records per page. At most 100, default 50.

  • cursor string

    The value of next_cursor from the page before.

Response

200 A page of entries. The fields are those of the f gas entry model.

Request
GET/units/{unit}/fgas-entries
curl https://api.maci.energy/v1/units/0b6f4c1e-5a1d-4a57-9f0e-2f6f3f0c9a11/fgas-entries \
  -H "Authorization: Bearer $MACI_API_KEY"
Response 200
{
  "data": [
    {
      "id": "e03018b5-1854-47dd-ac3b-1275002c8808",
      "unit_id": "0b6f4c1e-5a1d-4a57-9f0e-2f6f3f0c9a11",
      "type": "rum-for-varmt",
      "performed_at": "2026-10-30",
      "refrigerant": "R449A",
      "quantity_kg": 2.5,
      "reason": "Reason",
      "gas_origin": "Gas origin",
      "origin_facility_name": "Example Recovery A/S",
      "origin_facility_address": "Example Road 2, 8000 Aarhus",
      "origin_certificate_no": "R-2207",
      "method": "Method",
      "result": null,
      "leak_location": "Flare nut on the liquid line",
      "description": "Labour",
      "disposal": "Disposal",
      "company_name": "Example Cooling ApS",
      "company_cvr": "12345678",
      "company_certificate_no": "K-4471",
      "person_name": "Jonas L.",
      "person_certificate_no": "P-1182",
      "corrects_entry_id": null,
      "is_corrected": false,
      "created_at": "2026-10-30T09:15:00Z"
    }
  ],
  "next_cursor": null
}

POST/units/{unit}/fgas-entries

Create F-gas entry

New entry in the F-gas log.

Takes the certificates of the company and of the person. An entry cannot be changed afterwards. The unit has to have Premium.

Scope: fgas:write

Path parameters

  • unit string (uuid) required

    The ID of the unit.

Headers

  • Idempotency-Key string

    A value of your own choosing, so that a repeated call does not create two records.

Body

  • type string required

    One of installation, top_up, recovery, leak_check, leak_repair, detection_system_check, decommissioning

  • performed_at string (date) required

    The date of the work.

  • company_name string required

    The company that did the work.

  • company_certificate_no string required

    The certificate number of the company.

  • person_name string required

    The person who did the work.

  • person_certificate_no string required

    The certificate number of the person.

  • company_cvr string, nullable
  • refrigerant string

    The designation of the refrigerant. Needed for installation and top_up.

  • refrigerant_id string (uuid)

    Can be used instead of refrigerant.

  • quantity_kg number

    The quantity in kg. Needed for installation, top_up, recovery and decommissioning.

  • reason string

    Needed for top_up.

    One of service, leakage

  • gas_origin string

    Needed for top_up.

    One of virgin, recycled, reclaimed

  • origin_facility_name string

    Needed for recycled or reclaimed gas.

  • origin_facility_address string

    Needed for recycled or reclaimed gas.

  • origin_certificate_no string

    Needed for recycled or reclaimed gas.

  • method string

    Needed for leak_check.

    One of direct, indirect

  • result string

    For leak_check: tight or leak_found. For leak_repair: repaired or not_repaired. For detection_system_check: ok or fault.

  • leak_location string

    Needed when a leak check finds a leak.

  • description string

    Needed for leak_repair.

  • disposal string

    What happened to the refrigerant. Needed for decommissioning.

Response

201 The entry that was created. The fields are those of the f gas entry model.

Request
POST/units/{unit}/fgas-entries
curl -X POST https://api.maci.energy/v1/units/0b6f4c1e-5a1d-4a57-9f0e-2f6f3f0c9a11/fgas-entries \
  -H "Authorization: Bearer $MACI_API_KEY" \
  -H "Idempotency-Key: a-value-of-your-own" \
  -H "Content-Type: application/json" \
  -d '{
    "type": "installation",
    "performed_at": "2026-10-30",
    "company_name": "Example Cooling ApS",
    "company_certificate_no": "K-4471",
    "person_name": "Jonas L.",
    "person_certificate_no": "P-1182",
    "company_cvr": "12345678",
    "refrigerant": "R449A",
    "refrigerant_id": "2b7c4d1e-9f0a-4b3c-8d6e-5a4f3e2d1c0b",
    "quantity_kg": 2.5,
    "reason": "service",
    "gas_origin": "virgin"
  }'
Response 201
{
  "id": "e03018b5-1854-47dd-ac3b-1275002c8808",
  "unit_id": "0b6f4c1e-5a1d-4a57-9f0e-2f6f3f0c9a11",
  "type": "rum-for-varmt",
  "performed_at": "2026-10-30",
  "refrigerant": "R449A",
  "quantity_kg": 2.5,
  "reason": "Reason",
  "gas_origin": "Gas origin",
  "origin_facility_name": "Example Recovery A/S",
  "origin_facility_address": "Example Road 2, 8000 Aarhus",
  "origin_certificate_no": "R-2207",
  "method": "Method",
  "result": null,
  "leak_location": "Flare nut on the liquid line",
  "description": "Labour",
  "disposal": "Disposal",
  "company_name": "Example Cooling ApS",
  "company_cvr": "12345678",
  "company_certificate_no": "K-4471",
  "person_name": "Jonas L.",
  "person_certificate_no": "P-1182",
  "corrects_entry_id": null,
  "is_corrected": false,
  "created_at": "2026-10-30T09:15:00Z"
}

GET/units/{unit}/fgas-status

Get F-gas status

CO2 equivalent, check interval, latest and next leak check.

Scope: fgas:read

Path parameters

  • unit string (uuid) required

    The ID of the unit.

Response

200 Where the unit stands today. The fields are those of the f gas status model.

Request
GET/units/{unit}/fgas-status
curl https://api.maci.energy/v1/units/0b6f4c1e-5a1d-4a57-9f0e-2f6f3f0c9a11/fgas-status \
  -H "Authorization: Bearer $MACI_API_KEY"
Response 200
{
  "unit_id": "0b6f4c1e-5a1d-4a57-9f0e-2f6f3f0c9a11",
  "refrigerant": "R449A",
  "covered": true,
  "co2e_tonnes": 58.7,
  "interval_months": 6,
  "last_leak_check_at": "2026-10-30",
  "next_leak_check_due_at": "2026-10-30",
  "follow_up_check": null,
  "state": "State",
  "detection_system_missing": false
}